Mechanical
| Dimension (H x W x D): |
| DX2e-40M |
380 x 380 x 130 mm |
| DX2e-40MP |
380 x 380 x 130 mm |
| DX2e-40L |
620 x 380 x 130 mm |
| DX2e-40LP |
620 x 380 x 130 mm |
| Weight (Excluding batteries): |
| DX2e-40M(F) |
7 Kg |
| DX2e-40MP(F) |
7.2 Kg |
| DX2e-40L(F) |
9 Kg |
| DX2e-40LP(F) |
9.2 Kg |
Material:
1.2mm Zintec powder epoxy coated
Colour:
RAL 9001 - Cool Grey
Knockouts:
Top: 19 x M20
Bottom: 3 x M20
Temperature:
Operating: 0°C to +45°C
Storage: -10°C to +55°C
Relative humidity:
5% to 95% non-condensing
Electrical
Operating Voltage : 230Vac (+10%, -15%) 50-60 Hz
|
PSU Rating : |
| DX2e-40M(F) |
24 Vdc 4A |
| DX2e-40MP(F) |
24 Vdc 4A |
| DX2e-40L(F) |
24 Vdc 4A |
| DX2e-40LP(F) |
24 Vdc 4A |
| Stand-by Batteries : |
| DX2e-40M(F) |
2 x 7Ahr or 2 x 12AHr |
| DX2e-40MP(F) |
2 x 7Ahr or 2 x 12AHr |
| DX2e-40L(F) |
2 x 12AHr or 2 x 17AHr |
| DX2e-40LP(F) |
2 x 12AHr or 2 x 17AHr |
|
Auxiliary output *: +24 Vdc 250mA fused
Loop Capacity** : 2 Loops, 500mA per loop
126 devices per loop, Apollo Protocols
126 devices per loop, Hochiki ESP Protocol
198 devices per loop, Morley-IAS Protocol
198 devices per loop, System Sensor Protocol
Output Relays:
Fire relay : Single pole changeover 30Vdc 1A
Fault relay : Single pole changeover 30Vdc 1A
Aux relay : Programmable single pole changeover 30Vdc 1A
Onboard Inputs:
Keyswitch : programmable for select functions
Input #1 : programmable (monitored) for select functions
Input #2 : programmable (monitored) for select functions
Data Ports:
1 x RS 485 (Repeater connections)
1 x RS232 (PC Programming)
Sounder Circuits:
2 output circuits, 1A available across both sounder circuits.*
User interface
| Display : |
2 x 40 character backlit liquid crystal |
| Control keys : |
Sound Alarms, Silence/Resound, Mute Buzzer, Accept, Reset. |
| Programmable keys |
2 independent programmable buttons and LED indicators. |
| Programming keys: |
12 button alpha numeric key pad and 4 cursor keys. |
| Indicators : |
Fire, Fault, Test, Disablement, Delayed Mode, Alarms Silenced, Buzzer Muted, Sounders Disabled, Relays Disabled, Power Supply Fault, CPU Fault, Sounder Fault and Earth Fault. |
| Zonal : |
40 Fire zones LED indicators. |
Note:
* Maximum available current will be dependent on full control panel loading.
** Only one protocol can be selected within the control panel.
|